Daikin REYQ42P8Y1B [401/494] Operation lamp blinks

Daikin REYQ22P8Y1B [401/494] Operation lamp blinks
SiBE37-704_A Troubleshooting (OP: Unified ON/OFF Controller)
Troubleshooting 390
5. Troubleshooting (OP: Unified ON/OFF Controller)
5.1 Operation Lamp Blinks
Remote
Controller
Display
Operation lamp blinks
Applicable
Models
All indoor unit models
Unified ON/OFF controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
Supposed
Causes
Malfunction of transmission between optional central controller and indoor unit
Connector for setting master controller is disconnected
Defect of unified ON/OFF controller PCB
Defect of indoor unit PCB
Malfunction of air conditioner