Daikin REYQ42P8Y1B [358/494] Outdoor unit inverter over ripple protection

Daikin REYQ44P8Y1B [358/494] Outdoor unit inverter over ripple protection
Troubleshooting by Indication on the Remote Controller SiBE37-704_A
347 Troubleshooting
3.44
P1
Outdoor Unit: Inverter Over-Ripple Protection
Remote
Controller
Display
P1
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Imbalance in supply voltage is detected in PCB.
Imbalance in the power supply voltage causes increased ripple of voltage of the main circuit
capacitor in the inverter. Consequently, the increased ripple is detected.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"
P1
" will be displayed by pressing the inspection button.
When the amplitude of the ripple exceeding a certain value is detected for consecutive 4
minutes.
Supposed
Causes
Open phase
Voltage imbalance between phases
Defect of main circuit capacitor
Defect of inverter PCB
Defect of K2 relay in inverter PCB
Improper main circuit wiring