353 Troubleshooting
3.47
U0
Outdoor Unit: Gas Shortage Alert
Remote
Controller
Display
U0
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Detect gas shortage based on the temperature difference between low pressure or suction pipe
and heat exchanger.
Malfunction
Decision
Conditions
[In cooling mode]
Low pressure becomes 0.1MPa or below.
[In heating mode]
The degree of superheat of suction gas becomes 20 degrees and over.
SH= Ts1 –Te
Ts1: Suction pipe temperature detected by thermistor
Te : Saturated temperature corresponding to low pressure
Malfunction is not determined. The unit continues operation.
Supposed
Causes
Gas shortage or refrigerant clogging (piping error)
Defective thermistor (R4T, R7T, R12T, R15T)
Defective low pressure sensor
Defective outdoor unit PCB (A1P)