Daikin REYQ42P8Y1B [345/494] Outdoor unit malfunction of inverter radiating fin temperature rise

Daikin REYQ42P8Y1B [345/494] Outdoor unit malfunction of inverter radiating fin temperature rise
SiBE37-704_A Troubleshooting by Indication on the Remote Controller
Troubleshooting 334
3.39
L4
Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise
Remote
Controller
Display
L4
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Decision
Conditions
When the temperature of the inverter radiation fin increases above 87°C.
Supposed
Causes
Actuation of fin thermal (Actuates above 87°C)
Defect of inverter PCB
Defect of fin thermistor

Содержание

Скачать