SiBE37-704_A Test Operation
Test Operation 188
To energize the crankcase heater, make sure to turn the power ON at least 6 hours before
starting operation.
2. Press the BS1 MODE button once if the LEDs combination is not as in the figure below.
3. Press the BS4 TEST button once.
4. Hold the BS4 TEST button down for 5 seconds or more.
5. Charging mode judgement
However, if the indoor temperature is 10°C DB or lower, in some cases the unit will charge in
heating mode to increase the indoor temperature.
The unit will automatically select the cooling mode or heating mode for charging.
When charging in cooling mode, the unit will stop operating when the required amount of
refrigerant is charged.
During charging in heating mode, a person must manually close valve A before complete
charging is finished. The required amount is the calculated amount (see "6. Example of
connection (R-410A Type)" on page 464), therefore, the weight must be monitored
constantly.
Charging in heating mode
6. Start up
Wait while the unit is preparing for charging in heating mode.
It takes about 2 to 10 minutes for the system to become stable.
In case of a small charging amount, the system will start charging the refrigerant before the
system reaches the stable state. It may disturb a correct decision and may cause
overcharging.
7. Ready
Press the BS4 TEST button once within 5 minutes.
If the BS4 TEST button is not pushed within 5 minutes,
P2
will be displayed on the remote
controller. Refer to "3. Remote controller malfunction code display" on page 191.
8. Operation
When the following LED display is shown, open valve A and close the front panel. If the front
panel is left open, the system can not operate properly during the refrigerant charging.
When the refrigerant tank is not connected or is left with the valve closed for 30 minutes or
more, the outdoor unit will stop operation and the
P2
code will be displayed on the remote
controller of the indoor unit. Follow the procedure as described in "3. Remote controller
malfunction code display" on page 191.
= The state of this LED is not important.
H1P H2P H3P H4P H5P H6P H7P
hhkhhhh
H1P H2P H3P H4P H5P H6P H7P
kkkkkkk
H1P H2P H3P H4P H5P H6P H7P
Pressure control
(for the first minute)
hlhhhhk
Start up control
(for the next 2 minutes)
llhhhkh
Waiting for stable heating
conditions
(for the next ±15 minutes
(according to the system))
llhhhkk
H1P H2P H3P H4P H5P H6P H7P
llhhkhk
H1P H2P H3P H4P H5P H6P H7P
kl ∗∗∗∗∗