Daikin FHK35FJV1 [100/244] Equipment produces loud noise or shakes

Daikin FHK35FJV1 [100/244] Equipment produces loud noise or shakes
Si-71A Troubleshooting Based on Equipment Condition
Troubleshooting 89
3.9 Equipment Produces Loud Noise or Shakes
Applicable Model
All models of Skyair series
Error Detection
Method
Error Generating
Condition
Possible Cause
Excess charge of refrigerant
Air intrudes into refrigerant system
Flushing noise due to refrigerant shortage. (Sound of shooEE)
Troubleshooting
Correction of installation
Reinforcement for ceilings or walls
Insert shock absorber in mounting
section, or strengthen the mounting
section.
Normal. The sound is flushing noise of
gas (refrigerant) inside air conditioning
unit
Insert cushion materials to the pipe
support such as saddle.
Normal. The noise is a sound
generated at the time of gas
(refrigerant) flow change or stop
Disassemble and remove parts
contact.
Normal. Operation sound of draining
device
Correct piping manually or attach a
dead weight to pipe
Normal. Creak generates by
shrinkage of resin parts due to
temperature change.
Normal.
After vacuum drying, charge correct
amount of refrigerant.
* Excess charge of
refrigerant
* Air intrudes into
refrigerant system
* Flushing noise due to
refrigerant shortage.
(Sound of shoo...)
NO
YES
Does the
noise generate with
vibration of whole
ceilings and
walls?
YES
NO
NO
NO
Does the
noise generate
with vibration of
unit mounting
section?
Continuous
slight noise of
"shoo....." during
cooling or
defrosting
YES
YES
[Power supply side]
Is the
piping secured?
Sound
of "shoo..."
generates just after
operation start or stop,
or defrosting start
or stop.
YES
NO
NO
Does the fan
contact with other
parts?
Sound of
"shoo..." generates
during cooling or after
operation
stop.
YES
NO
NO
Does the
pipe contact with
casing?
Creak
during heating
and after operation
stop
YES
NO
YES
YES
NO
Is
the noise
flushing sound from
pressure reducing
valve or capillary
tube?
YES
[Installation work side]
(SF038)