Troubleshooting by Remote Controller Display / LED Display Si-71A
106 Troubleshooting
6.8 Malfunction of Heat Exchange Temperature Sensor System
Remote Controller
Display
&7
&7&7
&7
Applicable Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by heat exchanger sensor.
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed Causes
Failure of the sensor itself
Broken or disconnected wire
Failure of electronic circuitry (indoor unit PC board)
Failure of connector contact
Troubleshooting
Note:
Measure the resistance while referring to the thermistor temperature and resistance conversion table.
Thermistor temperature and resistance conversion table.
Disconnect the heat
exchange sensor
(R2T) from X18A on
the indoor unit PC
board and measure
the resistance.
Heat exchanger
senser
replacement
If contact is OK,
replace outdoor
unit PC board.
Is
the thermistor
normal?
(See note)
NO
YES
(SF010)
Temperature Suction, heat exchanger(indoor)
outdoor air, outdoor unit suction pipe
sensor (k
)
Temperature Suction, heat exchanger(indoor)
outdoor air, outdoor unit suction pipe
sensor (k
)
-6.0 90.8 28.0 17.6
-4.0 81.7 30.0 16.2
-2.0 73.5 32.0 14.8
0.0 66.3 34.0 13.6
2.0 59.8 36.0 12.5
4.0 54.1 38.0 11.5
6.0 48.9 40.0 10.6
8.0 44.3 42.0 9.8
10.0 40.2 44.0 9.1
12.0 36.5 46.0 8.4
14.0 33.2 48.0 7.8
16.0 30.2 50.0 7.2
18.0 27.5 52.0 6.9
20.0 25.1 54.0 6.2
22.0 23.0 56.0 5.7
24.0 21.0 58.0 5.3
26.0 19.2