Si-71A Operation Flowchart (RY71 - 140K)
Explanation of Function Operation 49
2. Operation Flowchart (RY71 - 140K)
2.1 Cooling/Program Dry Operation
Is safety
device in normal
condition?
Thermostat
ON Judgment
Is thermistor
in normal condition?
Is
cumulative retry total 6?
(See Section
5. 2. 5.)
Is discharge pipe
temperature high?
Is discharge
thermistor disconnected?
(See Section 5. 2. 7.)
NO
Thermostat OFF
Thermostat ON
YES
Power Switch ON
Initializing of Electronic
Expansion Valve
(See Section 5. 2. 4.)
Start Operation Using
Remote Controller.
Operation Mode Judgment
Four-Way Valve Control
(See Section 5. 2. 1.)
Startup Control
(See Section 5. 2. 11.)
Heating
Error Indication
NO
NO
NO
YES
To 1 To 2
YES
YES
NO
YES
Simulated Operation
(See Section 5. 2. 10.)
Shutdown
Due to Error
Thermostat OFF
(See Section 5. 2. 2.)
Emergency Operation
(See Section 5. 2. 2.)
Cooling/Dry
A
A
B
B
C
(SF027)