Existence of DIP Switch, Jumper and BS Si-71A
42 Explanation of Field Set
3. Existence of DIP Switch, Jumper and BS
3.1 Reference Table
Note:
Note 1
DIP Switch and BS Detail
Note:
Note 2
BS button (Pump down / Forced defrosting)
Pressing the BS button forcibly operates the air conditioner in the cooling mode.
1. To conduct a pump-down operation (sending refrigerant to outdoor unit), press the BS button to forcibly
operate the equipment in the cooling mode, then operate the unit for about 1 minute to stabilize the
system. After stabilizing system, close the liquid pipe stop valve on the outdoor unit, and after the
pressure decreases and the low pressure switch activates, close the gas pipe stop valve.
2. Forced defrost
To activate the defrost operation during the heating operation, press the BS button. This will activate
the forced defrost operation (cooling operation).
When the defrost cancel conditions are met, the equipment automatically switches off the defrost
operation.
Model PC Board Type DIP Switch Jumper BS
1213
Defrosting
Start Time
Changeover
Defrosting
Start
Temperature
Changeover
Thermostat
Control
Changeover
Long Piping
Correction
Changeover
Pump Down
Forced
Defrosting
R71KV1/Y1 EC9523/EC9524
{{
R71KVAL EC9523
{{
RY71KV1/Y1 EC9525/EC9526
{{{{{
R100~125KV1/Y1 EC9527/EC9528
{{
R100KVAL EC9527
{{
R125KTAL EC9528
{{
RY100~125KY1 EC9530
{{{{{
R140KY1/TAL EC9640
{{
RY140KY1/TAL EC9641
{{{{{
EMERGENCY
DEFROST
STARTING
SS1
HEAT
COOL
NORM
FORCED
DEF
PUMP
DOWN
BS1
OFF
ON
TEMP TIME
O
F
F
1
2
(SL042)