Yaskawa CIMR-UU4A0216F [104/644] Wiring checklist

Yaskawa CIMR-UU4A0302A [104/644] Wiring checklist
3.14 Wiring Checklist
No. Item Page(s)
Drive, Peripherals, Option Cards
1 Check drive model number to ensure receipt of correct model. 34
2 Make sure you have the correct peripheral devices. 412
3 Check the option card model number. 412
Installation Area and Physical Setup
4 Ensure that the area surrounding the drive complies with specifications. 50
Power Supply Voltage, Output Voltage
5 The voltage from the power supply should be within the input voltage specification range of the drive.
6 The voltage rating for the motor should match the drive output specifications.
34
515
7 Verify that the drive is properly sized to run the motor.
Main Circuit Wiring
8 Confirm proper branch circuit protection as specified by national and local codes. 66
9 Properly wire the power supply to drive terminals R/L1, S/L2, and T/L3. 69
10
Properly wire the drive and motor together.
The motor lines and drive output terminals U/T1, V/T2, and W/T3 should match in order to produce the desired phase
order. If the phase order is incorrect, the drive will rotate in the opposite direction.
85
11 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. 81
12
Use the correct wire gauges for the main circuit. Refer to Main Circuit Wire Gauges and Tightening Torque on page
81.
Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10
-3
If the cable between the drive and motor exceeds 50 m, adjust the carrier frequency set to C6-02 accordingly.
81
86
13 Properly ground the drive. 86
14 Tighten control circuit and grounding terminal screws. 81
15
Set up overload protection circuits when running multiple motors from a single drive.
M1
OL1
OL2
OLn
MC1
MC2
MCn
M2
Mn
Drive
MC1 - MCn
OL 1 - OLn
... magnetic contactor
... thermal relay
Power supply
Note: Close MC1 – MCn before operating the drive. MC1 – MCn cannot be switched off during run.
16
Verify that ground wiring for models UUoEoooo and UUoWoooo is correct before turning on the EMC filter
switch.
17 Verify phase advancing capacitors, input noise filters, or GFCIs are NOT installed on the output side of the drive.
Control Circuit Wiring
18 Use twisted-pair line for all drive control circuit wiring. 91
19
Ground the shields of shielded wiring to the GND
terminal.
91
20 For 3-Wire sequence, set parameters for multi-function contact input terminals S1 – S8, and wire control circuits.
21 Properly wire any option cards. 91
22 Check for any other wiring mistakes. Only use a multimeter to check wiring.
23 Properly fasten drive control circuit terminal screws. 81
24 Pick up all wire clippings.
25 Ensure that no frayed wires on the terminal block are touching other terminals or connections.
26 Properly separate control circuit wiring and main circuit wiring.
27 Analog signal line wiring should not exceed 50 m.