Yaskawa CIMR-UU4A0216F [308/644] N8 14 polarity compensation gain 3

Yaskawa CIMR-UU4A0240A [308/644] N8 14 polarity compensation gain 3
n
n8-14: Polarity Compensation Gain 3
Sets the gain for speed estimation. There is normally no need to change this parameter from the default value.
No. Name Setting Range Default
n8-14 Polarity Compensation Gain 3 0.000 to 10.000 1.000
n
n8-15: Polarity Compensation Gain 4
Sets the gain for speed estimation. There is normally no need to change this parameter from the default value.
No. Name Setting Range Default
n8-15 Polarity Compensation Gain 4 0.000 to 10.000 0.500
n
n8-21: Motor Ke Gain
Sets the gain for speed estimation. There is normally no need to change this parameter from the default value.
No. Name Setting Range Default
n8-21 Motor Ke Gain 0.80 to 1.00 0.90
n
n8-35: Initial Rotor Position Detection Selection
Selects how the rotor position is detected at start.
Note:
1. In CLV/PM,
the drive performs a magnetic pole search the first time it starts the motor. After that, rotor position is calculated from the
PG encoder signal and saved until the drive is switched off. Parameter n8-35 determines how this initial pole search operates.
2. High Frequency Injection and pulse injection for rotor position detection (n8-35 = 1 or 2) can be used with IPM motors only. When
using an SPM motor, select the pull in method to find the initial position of the rotor (n8-35 = 0).
3. This parameter is only available in AOLV/PM or CLV/PM.
No. Name Setting Range Default
n8-35 Initial Rotor Position Detection Selection 0 to 2 1
Setting 0: Pull In
Starts the rotor using pull-in current.
Setting 1: High Frequency Injection
High frequency is injected to detect the rotor position. Some noise may be generated from the motor at start.
Setting 2: Pulse Injection
A pulse signal is injected into the motor to detect the rotor position.
n
n8-36: High Frequency Injection Level
Sets the frequency level used for High Frequency Injection. Enabled when n8-57 = 1. There is normally no need to change
this parameter from the default value.
No. Name Setting Range Default
n8-36 High Frequency Injection Level 200 to 1000 Hz 500 Hz
n
n8-37: High Frequency Injection Amplitude
Sets
the amplitude
of high-frequency injection as a percentage of the voltage class standard (200 V Class: 200 V, 400 V Class:
400 V). Enabled when n8-57 = 1.
No. Name Setting Range Default
n8-37 High Frequency Injection Amplitude 0.0 to 50.0% 20.0%
n
n8-39: Low Pass Filter Cutoff Frequency for High Frequency Injection
Sets a cutoff frequency of a low pass filter for high frequency injection. Enabled when n8-57 = 1. There is normally no need
to change this parameter from the default value.
No. Name Setting Range Default
n8-39 Low Pass Filter Cutoff Frequency for High Frequency Injection 0 to 1000 Hz 50 Hz