3.8 Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and properly wire the main circuit in
the drive.
NOTICE: Do not solder
the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring practices
could result in drive malfunction due to loose terminal connections.
NOTICE: Do not switch the drive input to start or stop the motor. Frequently switching the drive on and off shortens the life of the DC bus
charge circuit and the DC bus capacitors, and can cause premature drive failures. For the full performance life, refrain from switching the
drive on and off more than once every 30 minutes.
u
Main Circuit Terminal Functions
Table 3.2 Main Circuit Terminal Functions
Drive Model
2o0028 to 2o0248 4o0011 to 4o0414
Function Page
Terminal Type
R/L1
Main circuit power supply input Connects line power to the drive 67S/L2
T/L3
U/T1
Drive output Connects to the motor 67V/T2
W/T3
p1, n1 Momentary power loss recovery unit input
Available for connecting a momentary power
loss recovery unit option
100 Ω or less 10 Ω or less Grounding terminal 86
u
Protecting Main Circuit Terminals
n
Insulation Caps or Sleeves
Use
insulation caps
or sleeves when wiring the drive with crimp terminals. Take particular care to ensure that the wiring does
not touch nearby terminals or the surrounding case.
n
Main Circuit Protective Cover
Close the protective cover after wiring the main circuit terminals on 2o0028 to 2o0081 and 4o0011 to 4o0077.
Figure 3.23 Main Circuit Protective Cover (Models 2o0028 to 2o0081 and 4o0011 to 4o0077)
Attach the protective covers after wiring the main circuit terminals and p1, and n1 terminals on models 2o0104 to 2o0248
and 4o0096 to 4o0414.
3.8 Main Circuit Wiring
80