Yaskawa CIMR-UU4A0216F [123/644] Start up flowcharts

Yaskawa CIMR-UU4A0040A [123/644] Start up flowcharts
YES
NO
From
Flowchart
A
Possible for motor to
rotate during tuning? <1>
<2>
Motor test report/
data sheet available?
Perform Stationary
Auto-Tuning 2 (T1-01 = 4)
Perform Rotating
Auto-Tuning (T1-01 = 0)
Is there a PG
encoder on the
motor?
Perform Inertia Tuning
(T1-01 = 8) <4>
Should the
drive set ASR gain
automatically?
Return to
Flowchart
A
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Run the operation in test mode for Auto-Tuning 3.
Connect the load to the motor.
Perform ASR gain tuning.
(T1-01 = 9) <5>
Run the machine and check for desired
operation.
NO
NO
YES
YES
YES
YES
NO
Does the
application require
Feed Forward
Function?
Obtain a test report from the motor manufacturer
and perform Stationary Auto-Tuning 2 (T1-01 = 4).
Perform Stationary
Auto-Tuning 3 (T1-01 = 5) <3>
YES
NO
NO
Is the load less than
30% of the rated load
for the motor?
Figure 4.10 Flowchart A2: High Performance Operation Using OLV or CLV
<1>
Decouple the load from the motor to properly perform Rotational Auto-Tuning
<2>
Rotational Auto-Tuning can still be performed if the load is 30% or smaller, though Stationary Auto-Tuning may yield better
control performance.
<3>
Run the operation in test mode for Auto-Tuning 3. The drive will set motor parameters automatically. Refer to Stationary Auto-
Tuning 3 on page 134 for details.
<4> Make sure the motor and load can run freely, i.e., if a brake is mounted, make sure it is released.
<5> ASR Gain Tuning automatically performs Inertia Tuning and sets parameters related to the Feed Forward function.
4.4 Start-Up Flowcharts
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual