Yaskawa CIMR-UU4A0216F [235/644] F1 18 dv3 detection selection clv pm

Yaskawa CIMR-UU4A0040A [235/644] F1 18 dv3 detection selection clv pm
r/min =
Input pulse frequency from PG 60
Pulses per Rev (F1-01/31)
Load-side PG gear teeth (F1-12/33)
Motor-side PG gear teeth (F1-13/34)
No. Parameter Name Option Port Setting Range Default
F1-12 PG 1 Gear Teeth 1 CN5-C 0 to 1000 0
F1-13 PG 1 Gear Teeth 2 CN5-C 0 to 1000 0
F1-33 PG 2 Gear Teeth 1 CN5-B 0 to 1000 0
F1-34 PG 2 Gear Teeth 2 CN5-B 0 to 1000 0
Note: A gear ratio of 1 will be used if any of these parameters are set to 0.
n
F1-18: dv3 Detection Selection (CLV/PM)
Sets the number of times the drive will detect a dv3 situation before triggering a dv3 fault. The drive detects a dv3 condition
when
the torque
reference and speed reference are in opposite directions while the difference between the actual motor speed
and the speed reference is greater than 30%. Setting F1-18 to 0 disables dv3 detection.
No. Parameter Name Option Port Setting Range Default
F1-18 dv3 Detection Selection CN5-B, CN5-C 0 to 10 10
Note: A common cause for a dv3 fault is the incorrect setting of E5-11. Make sure to enter the correct Z Pulse offset to E5-11.
n
F1-19: dv4 Detection Selection (CLV/PM)
Sets the number of pulses necessary to trigger a dv4 fault when there is a motor speed deviation opposite to the frequency
reference. Setting F1-19 to 0 disables dv4 detection.
No. Parameter Name Option Port Setting Range Default
F1-19 dv4 Detection Selection CN5-B, CN5-C 0 to 5000 128
Note: 1. A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure to enter the correct Z-pulse offset to E5-11.
2. Set F1-19 to 0 for applications where the direction of the load is the opposite of the speed reference.
n
F1-20, F1-36: PG Option Card Disconnect Detection
Sets whether the drive detects a PG hardware fault (PGoH).
No. Parameter Name Option Port Setting Range Default
F1-20 PG Option Card Disconnection Detection 1 CN5-C 0, 1 1
F1-36 PG Option Card Disconnection Detection 2 CN5-B 0, 1 1
Setting 0: Disabled
Setting 1: Enabled
n
F1-21, F1-37: PG 1, PG 2 Signal Selection (V/f w/PG only)
Determines whether the signal to the PG option card is single-channel or two-channel.
No. Parameter Name Option Port Setting Range Default
F1-21 PG 1 Signal Selection CN5-C 0, 1 0
F1-37 PG 2 Signal Selection CN5-B 0, 1 0
Setting 0: Single-channel (A channel only)
Setting 1: Two-channel (channels A and B)
n
F1-30: PG Option Card Port for Motor 2 Selection
Specifies
the
drive
port for the PG option card used for motor 2. Set this parameter when switching between motor 1 and motor
2, where both motors supply a speed feedback signal to the drive. Set F1-30 to 0 when using the same PG card for feedback
signals from both motors. Set F1-30 to 1 when each motor has its own PG card connected to the drive.
Note: The motor 2 selection function cannot be used with PM motors.
5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
235
5
Parameter Details