Yaskawa CIMR-UU4A0216F [512/644] O3 copy function

Yaskawa CIMR-UU4A0040A [512/644] O3 copy function
No.
(Addr.
Hex)
Name LCD Display Description Values Page
o2-03
(0507)
User Parameter Default
Value
User Default Sel
0: No Change
1: Save User Init
2: Clear User Init
All Modes
0: No change.
1: Set defaults. Saves parameter settings as default values for a
User Initialization.
2: Clear all. Clears the default settings that have been saved for
a User Initialization.
Default: 0
Range: 0 to 2
314
o2-04
(0508)
Drive Model Selection Inverter Model #
All Modes
Enter the drive model. Setting required only if installing a new
control board.
Default:
Determined by
drive capacity
314
o2-05
(0509)
Frequency Reference
Setting Method
Selection
Oper Ref Method
0: Disabled
1: Enabled
All Modes
0: ENTER key must be pressed to enter a frequency reference.
1: ENTER key is not required. The frequency reference can be
adjusted using the up and down arrow keys only.
Default: 0
Range: 0, 1
314
o2-06
(050A)
Operation Selection
when Digital Operator
is
Disconnected
Oper Discon Det
0: Disabled
1: Enabled
All Modes
0: The drive continues operating if the digital operator is
disconnected.
1: An oPr fault is triggered and the motor coasts to stop.
Default: 1
Range: 0, 1
315
o2-07
(0527)
Motor Direction at
Power Up when Using
Operator
For/RevSel@PwrUp
0: Forward
1: Reverse
All Modes
0: Forward
1: Reverse
This parameter requires assigning drive operation to the digital
operator.
Default: 0
Range: 0, 1
315
o2-09
(050D)
Factory use.
u
o3: Copy Function
No.
(Addr.
Hex)
Name LCD Display Description Values Page
o3-01
(0515)
Copy Function Selection
COPY SELECT
0: COPY SELECT
1: INV→OP READ
2: OP→INV WRITE
3: OP←→INV
VERIFY
All Modes
0: Copy select
1: INV → OP READ (Read parameters from the drive, saving
them onto the digital operator).
2: OP → INV WRITE (Copy parameters from the digital
operator, writing them to the drive).
3: OP INV VERIFY (Verify that parameter settings match the
data saved on the operator).
To read the drive parameter settings into the digital operator, set
o3-02 to 1 (to allow reading).
Default: 0
Range: 0 to 3
315
o3-02
(0516)
Copy Allowed Selection
Read Allowable
0: Disabled
1: Enabled
All Modes
Selects whether the read operation (o3-01 = 1) is enabled or
disabled.
0: Read operation prohibited
1: Read operation allowed
Default: 0
Range: 0, 1
316
u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name LCD Display Description Values Page
o4-01
(050B)
Cumulative Operation
Time Setting
DrvElapsTimeCnt
All Modes
Sets the value for the cumulative operation time of the drive in
units of 10 h.
Default: 0
Min.: 0
Max.: 9999
316
o4-02
(050C)
Cumulative Operation
Time Selection
ElapsTimeCntSet
0: Power-On Time
1: Running Time
All Modes
0: Logs power-on time
1: Logs operation time when the drive output is active (output
operation time).
Default: 0
Range: 0, 1
316
B.12 o: Operator-Related Settings
512
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual