Status Description
Open Output frequency is more than or equal to the minimum output frequency set to E1-09 or b2-01
Closed Output frequency becomes less than the minimum output frequency set to E1-09 or b2-01
Note: When using CLV
or CLV/PM control modes, the output terminal closes when the motor speed becomes less than or equal to the zero speed
level set for b2-01. In all other control modes, the output terminal closes when the output frequency becomes less than or equal to the
minimum output frequency set for E1-09.
OFF
Output frequency
or
motor speed
Zero Speed
ON
E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)
Figure 5.67 Zero-Speed Time Chart
Setting 2: Speed Agree 1 (f
ref
/f
out
Agree 1)
Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status Description
Open Output frequency or motor speed does not match the frequency reference while the drive is running.
Closed Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note: Detection works in forward and reverse.
L4-02
L4-02
Frequency
reference
Speed agree 1
ON
OFF
Output Frequency
or Motor Speed
Figure 5.68 Speed Agree 1 Time Chart
Refer to L4-01, L4-02: Speed Agree Detection Level and Detection Width on page 289 for more details.
Setting 3: User-Set Speed Agree 1 (f
ref
/f
set
Agree 1)
Closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Status Description
Open Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.