Simplified Setup Using the Setup Group
The Setup Group lists the basic parameters necessary to set up the drive for an application. This group expedites the startup
process for an application by showing only the most important parameters for the application.
n
Using the Setup Group
Figure 4.7 illustrates how to enter and how to change parameters in the Setup Group.
The
first display shown when entering the Setup Group is the Application Selection menu. Skipping this display will keep the
current Setup Group parameter selection. The default setting for the Setup Group is a group of parameters most commonly
use in general-purpose applications. Pressing the ENTER key from the Application Selection menu and selecting an
Application Preset will change the Setup Group to parameters optimal for the application selected. Refer to Application
Selection on page 127.
In this example, the Setup Group is accessed to change b1-01 from 1 to 0. This changes the source of the frequency reference
from the control circuit terminals to the digital operator.
Control Circuit
Terminal
Parameter Display
Operator
<1>
<2>
<2>
Frequency reference
appears when
powered up
Press until
Setup Group
appears
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
HELP
- MODE - PRG
Quick Setting
DATA
FWD
Entry Accepted
- SETUP -
b1-01= 1 *1*
Analog Input
PRG
Ref Source 1
Home FWD DATA
- SETUP -
A1-06= 0 *0*
General
PRG
Application Sel
Home FWD DATA
- SETUP -
A1-02= 2 *2*
Open Loop Vector
PRG
Control Method
Home FWD DATA
- SETUP -
b1-02= 1 *1*
Digital Inputs
PRG
Run Source 1
Home FWD DATA
- SETUP -
L3-04= 1 *1*
General Purpose
PRG
StallP Decel Sel
Home FWD DATA
“1”
- SETUP -
b1-01= 1 *1*
Analog Input
PRG
Ref Source 1
FWD
“1”
- SETUP -
b1-01= 0 *1*
Operator
PRG
Ref Source 1
FWD
FWD
JOG
Figure 4.7 Setup Group Example
<1> Use the up
and down arrow keys to scroll through the Setup Group. Press the ENTER key to view or change parameter settings.
<2> To return to the previous menu without saving changes, press the ESC key.
4.3 The Drive and Programming Modes
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
117
4
Start-Up Programming
& Operation