Yaskawa CIMR-UU4A0216F [142/644] Parameter settings during inertia and speed control loop auto tuning t3

Yaskawa CIMR-UU4A0065A [142/644] Parameter settings during inertia and speed control loop auto tuning t3
n
T2-14: PM Motor Induced Voltage Constant (Ke)
Enter the motor induced voltage constant (Ke).
No. Name Setting Range Default
T2-14 PM Motor Induced Voltage Constant (Ke) 0.0 to 2000.0 Determined by T2-02
n
T2-15: Pull-In Current Level for PM Motor Tuning
Sets
the
amount of pull-in current used to tune the d-Axis and q-Axis inductance. Set as a percentage of the motor rated current.
No. Name Setting Range Default
T2-15 Pull-In Current Level for PM Motor Tuning 0 to 120% 30%
n
T2-16: PG Number of Pulses Per Revolution for PM Motor Tuning
Enter
the
number of pulses from the PG encoder per motor rotation. Set the actual number of pulses for one full motor rotation.
No. Name Setting Range Default
T2-16 PG Number of Pulses Per Revolution for PM Motor Tuning 0 to 15000 ppr 1024 ppr
n
T2-17: Encoder Z Pulse Offset (ΔΘ)
Sets the amount of compensation or offset in 0.1 degree units to fine-tune the home position. Perform Z Pulse tuning when
the amount of offset needed for the Z Pulse is unknown or if the PG encoder is replaced.
No. Name Setting Range Default
T2-17 Encoder Z Pulse Offset (ΔΘ) -180.0 to 180.0 deg 0.0 deg
u
Parameter Settings during Inertia and Speed Control Loop Auto-Tuning: T3
These tuning methods apply a sine wave test signal to the system. The drive estimates the system inertia by the measuring the
response and automatically sets the parameters listed in Table 4.22.
Table 4.22 Parameters Adjusted by Inertia and Speed Loop Auto-Tuning
Parameter Description
T1-01 or T2-01
8
Inertia Tuning
9
Speed Control Loop (ASR)
Tuning
C5-01 ASR Proportional Gain 1 YES
C5-17 (C5-37) Motor Inertia YES YES
C5-18 (C5-38) Motor Inertia Ratio YES YES
n5-02 Motor Acceleration Time YES YES
n5-03 Feed Forward Control Ratio Gain YES YES
n
T3-01: Inertia Tuning Frequency Reference
Sets
the
frequency of the test signal applied to the motor during Inertia Tuning. Although this setting rarely needs to be changed,
increasing the value may be beneficial when working with high inertia loads.
No. Name Setting Range Default
T3-01 Inertia Tuning Frequency Reference 0.1 to 20.0 Hz 3.0 Hz
n
T3-02: Inertia Tuning Reference Amplitude
Enter the amplitude of the test signal applied to the motor during Inertia Tuning. Although this setting rarely needs to be
changed,
decrease
the setting if a large load inertia causes problems during Inertia Tuning. Adjust T3-02 if a fault occurs when
T3-01 is set to a low value.
No. Name Setting Range Default
T3-02 Inertia Tuning Reference Amplitude 0.1 to 10.0 rad 0.5 rad
4.7 Auto-Tuning
142
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual