Yaskawa CIMR-UU4A0216F [225/644] E2 04 number of motor poles

Yaskawa CIMR-UU4A0156F [225/644] E2 04 number of motor poles
No. Parameter Name Setting Range Default
E2-03 Motor No-Load Current
0.00 A to [E2-01]
<1>
Determined by
C6-01 and o2-04
<1> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units
n
E2-04: Number of Motor Poles
Set
the number
of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No. Parameter Name Setting Range Default
E2-04 Number of Motor Poles 2 to 48 4
n
E2-05: Motor Line-to-Line Resistance
Sets the
line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is automatically
calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it manually.
When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75 °C.
F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115 °C.
No. Parameter Name Setting Range Default
E2-05 Motor Line-to-Line Resistance 0.000 to 65000 mΩ
Determined by
C6-01 and o2-04
n
E2-06: Motor Leakage Inductance
Sets
the voltage
drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically set
during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 2, 3).
No. Parameter Name Setting Range Default
E2-06 Motor Leakage Inductance 0.0 to 40.0%
Determined by
C6-01 and o2-04
n
E2-07: Motor Iron-Core Saturation Coefficient 1
Sets the
motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then
this value is automatically calculated and set to E2-07. This coefficient is used when operating with constant output.
No. Parameter Name Setting Range Default
E2-07 Motor Iron-Core Saturation Coefficient 1 0.00 to 0.50 0.50
n
E2-08: Motor Iron-Core Saturation Coefficient 2
Sets the
motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully, then
this value is automatically calculated and set to E2-08. This coefficient is used when operating with constant output.
No. Parameter Name Setting Range Default
E2-08 Motor Iron-Core Saturation Coefficient 2 E2-07 to 0.75 0.75
n
E2-09: Motor Mechanical Loss
Sets the motor mechanical loss as a percentage of motor rated power (kW) capacity.
Adjust this setting in the following circumstances:
When there is a large amount of torque loss due to motor bearing friction.
When there is a large amount of torque loss in a fan or pump application.
The setting for the mechanical loss is added to the torque.
5.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
225
5
Parameter Details