Yaskawa CIMR-UU4A0216F [260/644] H terminal functions

Yaskawa CIMR-UU2A0104A [260/644] H terminal functions
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
or Motor Speed
Figure 5.71 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agree Detection Level and Detection Width on page 289 for more details.
Setting 6: Drive Ready
The output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
When the power is shut off
During a fault
When the internal power supply of the drive has malfunctioned
When a parameter setting error makes it impossible to run
Although stopped, an undervoltage situation occurs
While editing a parameter in the Programming Mode (when b1-08 = 0)
Setting 7: During Power Supply Voltage Fault
Output closes when the power supply voltage or the control circuit voltage falls below the drive operating voltage or when
the power supply frequency is incorrect.
Status Description
Open Normal
Closed
One of the following faults will occur:
Fdv (Power Supply Frequency Fault)
AUv (Power Supply Undervoltage)
Uv (Undervoltage)
Setting 8: During Baseblock (N.O.)
The output closes
to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Status Description
Open Drive is not in a baseblock state.
Closed Baseblock is being executed.
Setting 9: Frequency Reference Source
Displays the currently selected frequency reference source.
Status Description
Open Frequency reference is provided from External reference 1 (b1-01) or External reference 2 (b1-15).
Closed Frequency reference is being sourced from the digital operator.
Setting A: Run Command Source
Displays the currently selected Run command source.
Status Description
Open Run command is provided from External reference 1 (b1-02) or 2 (b1-16).
Closed Run command is being sourced from the digital operator.