Yaskawa CIMR-UU4A0216F [610/644] Safety standards

Yaskawa CIMR-UU4A0216F [610/644] Safety standards
D.4 Safe Disable Input
u
Safe Disable Input Function
This section explains the Safe Disable function. Contact Yaskawa if more information is required.
n
Safety Standards
The TUV mark indicates compliance with safety standards.
Figure D.7 TUV Mark
Table D.7 Safety Standards and Applicable Harmonized Standards
Safety Standards Applicable Harmonized Standards
Functional Safety
IEC/EN 61508 series: 2010 (SIL3)
IEC/EN 62061: 2005 (SILCL3)
IEC/EN 61800-5-2: 2007 (SIL3)
Safety of Machinery ISO/EN ISO 13849-1/AC: 2009 (PL e (Cat.3))
EMC IEC/EN 61326-3-1: 2008 (EMC-related)
The Safe Disable function is in compliance with these standards.
n
Specifications
The Safe Disable inputs provide a stop function in compliance with “Safe Torque Off” as defined in the IEC/EN 61800-5-2.
Safe Disable inputs have been designed to meet the requirements of the ISO/EN 13849-1 and IEC/EN 61508.
A Safe Disable Status Monitor for error detection in the safety circuit is also provided.
Table D.8
Specifications for Safe Disable Function
Inputs/Outputs
Input signal specifications
Signal ON level: 18 to 28 Vdc
Signal OFF level: -4 to 4 Vdc
Inputs: 2
Safe Disable inputs H1, H2
Outputs: 1
Safe Disable Monitor output EDM (DM+, DM-)
Response Time from Input Open to Drive
Output Stop
Shorter than 3 ms
Response Time from Input Open of H1 and H2
Terminals to EDM
Shorter than 4 ms
Failure Probability
Demand Rate Low
PFD = 8.14E
-6
Demand Rate High/
Continuous
PFH = 1.96E
-9
Performance Level
The Safe Disable inputs satisfy the following requirements (DC from EDM considered) Performance
Level (PL) e according to ISO/EN 13849-1
HFT (Hardware Fault Tolerance) N = 1
Classification of Subsystem Type B
u
Precautions
DANGER! Sudden Movement Hazard.
Improper use of the Safe Disable function can result in serious injury or even death. Make sure the
whole system or machinery in which the Safe Disable function is used complies with safety requirements. When implementing the Safe
Disable function into the safety system of a machine, perform a thorough risk assessment for the entire system to assure compliance with
relevant safety norms.
D.4 Safe Disable Input
610
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual