Yaskawa CIMR-UU4A0216F [300/644] L8 27 overcurrent detection gain

Yaskawa CIMR-UU4A0011F [300/644] L8 27 overcurrent detection gain
No. Name Setting Range Default
L8-19 Frequency Reduction Rate During Overheat Pre-Alarm 0.1 to 0.9 0.8
n
L8-27: Overcurrent Detection Gain
Adjusts the overcurrent detection level in OLV/PM, AOLV/PM, or CLV/PM. A setting of 100% is equal to the motor rated
current. When the drive rated current is considerably higher than the motor rated current, use this parameter to decrease the
overcurrent level and prevent motor demagnetization from high current.
Overcurrent
detection uses
the lower value between the overcurrent level for the drive and the motor rated current multiplied
by L8-27.
Note: The drive detects the lowest overcurrent from the overcurrent level of the drive, the setting value of this parameter, and the overcurrent
level determined from the motor rated current.
No. Name Setting Range Default
L8-27 Overcurrent Detection Gain 0.0 to 400.0% 300.0%
n
L8-29: Current Unbalance Detection (LF2)
Enables
and disables
output current unbalance detection in OLV/PM, AOLV/PM, or CLV/PM. Current unbalance can heat a
PM motor and demagnetize the magnets. The current unbalance detection function monitors output current and triggers the
LF2 fault to prevent such motor damage.
No. Name Setting Range Default
L8-29 Current Unbalance Detection (LF2) 0, 2 2
Setting 0: Disabled
Motor protection with LF2 is disabled.
Setting 2: Enabled
LF2 fault is triggered when an output current imbalance is detected. Drive output shuts off and the motor coasts to stop.
n
L8-32: Cooling Fan Failure Selection
Determines drive operation when a FAn fault occurs.
No. Name Setting Range Default
L8-32 Cooling Fan Failure Selection 0 to 2 1
Setting 0: Ramp to Stop
The drive stops the motor using the deceleration time 1 set in parameter C1-02.
Setting 1: Coast to Stop
The drive output is switched off and the motor coasts to a stop.
Setting 2: Fast Stop
The drive stops the motor using the Fast stop time set in parameter C1-09.
n
L8-35: Installation Method Selection
Selects the type of installation for the drive and changes the drive overload (oL2) limits accordingly.
Note:
1. Initialization does not reset this parameter.
2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or
when mounting a standard drive with the heatsink outside the cabinet.
No. Name Setting Range Default
L8-35 Installation Method Selection 0, 2, 3
<1>
<1> Default setting is determined by parameter o2-04, Drive Model Selection.
Setting 0: IP00/Open-Chassis Enclosure
For an Open Type enclosure drive installed with at a minimum of 30 mm space to the next drive or a cabinet wall.
Setting 2: IP20/NEMA Type 1 Enclosure
For drives compliant with IP20/NEMA Type 1 enclosure specifications.
5.8 L: Protection Functions
300
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual