Yaskawa CIMR-UU4A0216F [502/644] L5 fault restart

Yaskawa CIMR-UU4A0011A [502/644] L5 fault restart
No.
(Addr.
Hex)
Name LCD Display Description Values Page
L4-05
(049D)
Frequency Reference
Loss Detection Selection
Ref Loss Sel
0: Stop
1:
Run@L4-06PrevRef
All Modes
0: Stop. Drive stops when the frequency reference is lost.
1: Run. Drive runs at a reduced speed when the frequency
reference is lost.
Default: 0
Range: 0, 1
290
L4-06
(04C2)
Frequency Reference at
Reference Loss
Fref at Floss
All Modes
Sets the percentage of the frequency reference that the drive
should run with when the frequency reference is lost.
Default: 80.0%
Min.: 0.0
Max.: 100.0
290
L4-07
(0470)
Speed Agree Detection
Selection
Freq Detect Sel
0: No Detection
@BB
1: Always Detected
All Modes
0: No detection during baseblock.
1: Detection always enabled.
Default: 0
Range: 0, 1
290
<1> Default setting is determined by parameter A1-02, Control Method Selection.
u
L5: Fault Restart
No.
(Addr.
Hex)
Name LCD Display Description Values Page
L5-01
(049E)
Number of Auto Restart
Attempts
Num of Restarts
All Modes
Sets the number of times the drive may attempt to restart after the
following faults occur: GF, LF, oC, oH1, oL1, oL3, oL4, ov, Sto,
Uv1.
Default: 0
Min.: 0
Max.: 10
291
L5-02
(049F)
Auto Restart Fault
Output Operation
Selection
Restart Sel
0: Flt Outp Disabld
1: Flt Outp Enabled
All Modes
0: Fault output not active.
1: Fault output active during restart attempt.
Default: 0
Range: 0, 1
291
L5-04
(046C)
Fault Reset Interval
Time
Flt Reset Wait T
All Modes
Sets the amount of time to wait between performing fault restarts.
Default: 10.0 s
Min.: 0.5
Max.: 600.0
292
L5-05
(0467)
Fault Reset Operation
Selection
Fault Reset Sel
0: Continuous
1: Use L5-04 Time
All Modes
0: Continuously attempt to restart while incrementing restart
counter only at a successful restart (same as F7 and G7).
1: Attempt to restart with the interval time set in L5-04 and
increment the restart counter with each attempt (same as V7).
Default: 0
Range: 0, 1
292
u
L6: Torque Detection
No.
(Addr.
Hex)
Name LCD Display Description Values Page
L6-01
(04A1)
Torque Detection
Selection 1
Torq Det 1 Sel
0: Disabled
1: OL Alm at SpdAgr
2: OL Alm dur RUN
3: OL Flt at SpdAgr
4: OL Flt dur RUN
5: UL Alm at SpdAgr
6: UL Alm dur RUN
7: UL Flt at SpdAgr
8: UL Flt dur RUN
All Modes
0: Disabled
1: oL3 detection only active during speed agree, operation
continues after detection
2: oL3 detection always active during run, operation continues
after detection
3: oL3 detection only active during speed agree, output shuts
down on an oL3 fault
4: oL3 detection always active during run, output shuts down on
an oL3 fault
5: UL3 detection only active during speed agree, operation
continues after detection
6: UL3 detection always active during run, operation continues
after detection
7: UL3 detection only active during speed agree, output shuts
down on a UL3 fault
8: UL3 detection always active during run, output shuts down on
a UL3 fault
Default: 0
Range: 0 to 8
293
L6-02
(04A2)
Torque Detection
Level 1 Torq Det 1 Lvl
All Modes
Sets the overtorque and undertorque detection level.
Default: 150%
Min.: 0
Max.: 300
294
B.10 L: Protection Function
502
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual