Yaskawa CIMR-UU4A0216F [298/644] An output phase loss fault lf is triggered when one output phase is lost the output shuts off and the motor coasts to stop

Yaskawa CIMR-UU2A0081F [298/644] An output phase loss fault lf is triggered when one output phase is lost the output shuts off and the motor coasts to stop
10 s
etc.
time
10 s 10 s 10 s 10 s 10 s 10 s
f
ref
× (L8-19)
f
ref
× (L8-19)
2
f
ref
× (L8-19)
4
f
ref
× (L8-19)
3
f
ref
Output frequency
Reset oH
Alarm
Reset oH
Alarm
Digital output (4D)
oH
Alarm
oH
Alarm
oH
Alarm
oH
Alarm
oH alarm number
Figure 5.102 Output Frequency Reduction During Overheat Alarm
n
L8-07: Output Phase Loss Protection Selection
Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.
Note: 1. Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable
this parameter in such cases.
2. Output phase loss detection is not possible when the drive is running a PM motor with light load.
No. Name Setting Range Default
L8-07 Output Phase Loss Protection Selection 0 to 2 1
Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost
An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.
Setting 2: Fault when Two Phases Are Lost
An output phase
loss fault (LF) is triggered when two or more output phases are lost. The output shuts off and the motor coasts
to stop.
n
L8-09: Output Ground Fault Detection Selection
Enables or disables the output ground fault detection.
No. Name Setting Range Default
L8-09 Output Ground Fault Detection Selection 0, 1 1
Setting 0: Disabled
Ground faults are not detected.
Setting 1: Enabled
A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.
n
L8-10: Heatsink Cooling Fan Operation Selection
Selects the heatsink cooling fan operation.
No. Name Setting Range Default
L8-10 Heatsink Cooling Fan Operation Selection 0, 1 0
5.8 L: Protection Functions
298
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual