T3-03: Motor Inertia
Enter
the
inertia of the motor. This value is used to determine the load inertia using the test signal response. The default setting
is for a Yaskawa standard motor as listed in the motor inertia table.
No. Name Setting Range Default
T3-03 Motor Inertia
0.0001 to 600.00 kgm
2
Determined by o2-04,
C6-01, E5-01
Note: Display is in the following units:
Models 2o0028 to 2o0130 and 4o0011 to 4o0077: 0.0001 kgm
2
units
Models 2o0154 to 2o0248 and 4o0096 to 4o0414: 0.001 kgm
2
units
Display resolution depends on the rated output current of the drive after setting drive duty using parameter C6-01.
n
T3-04: ASR Response Frequency
Sets
the
response frequency (reciprocal of the step response time constant) of the system or the connected machine. The drive
uses this value and the load inertia to fine-tune the speed control loop gain (C5-01, ASR Gain 1). Oscillation may result if the
value input here is higher than the actual response frequency of the system.
No. Name Setting Range Default
T3-04 ASR Response Frequency 0.1 to 50.0 Hz 10.0 Hz