Yaskawa CIMR-UU4A0216F [525/644] U5 pid monitors

Yaskawa CIMR-UU2A0081A [525/644] U5 pid monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U4-21
(07DD)
Run Command Source
Selection
Run Cmd Source
All Modes
Displays the source for the Run command as XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Digital operator
1 = External terminals
3 = MEMOBUS/Modbus communications
4 = Communication option card
7 = DWEZ
nn: Run command limit status data
00: No limit status.
01: Run command was left on when stopped in the PRG mode
02: Run command was left on when switching from LOCAL to
REMOTE operation
03: Waiting for soft charge bypass contactor after power up (Uv
or Uv1 flashes after 10 s)
04: Waiting for “Run command prohibited” time period to end
05: Fast Stop (digital input, digital operator)
06: b1-17 (Run command given at power-up)
07: During baseblock while coast to stop with timer
08: Frequency reference is below minimal reference during
baseblock
09: Waiting for Enter command
No signal output
available
U4-22
(07DE)
MEMOBUS/Modbus
Communications
Reference
MEMOBUS Ref Reg
All Modes
Displays the drive control data set by MEMOBUS/Modbus
communications register no. 0001H as a four-digit hexadecimal
number.
No signal output
available
U4-23
(07DF)
Communication Option
Card Reference
Option Ref Reg
All Modes
Displays drive control data set by an option card as a four-digit
hexadecimal number.
No signal output
available
<1> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 0099H.
<2> The MEMOBUS/Modbus communications data is in 10 h units. If data in 1 h units are also required, refer to register number 009BH.
<3> Display is in the following units:
2
o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units
<4> The values of U1-03, U2-05, and U4-13 are displayed on the digital operator in units of amperes. When those monitors are checked using
MEMOBUS/Modbus communications, the monitor values in MEMOBUS/Modbus communications are displayed as: numeric value / 8192 × drive
rated current (A) from the condition “192 (maximum value) = drive rated current (A)”
<5> When reading the value of this monitor via MEMOBUS/Modbus a value of 8192 is equal to 100% of the drive rated output current.
u
U5: PID Monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U5-01
(0057)
PID Feedback PID Feedback 1
All Modes
Displays the PID feedback value.
10 V: 100%
(-10 to +10 V)
0.01%
U5-02
(0063)
PID Input PID Input
All Modes
Displays the amount of PID input (deviation between PID
setpoint and feedback).
10 V: 100%
(-10 to +10 V)
0.01%
U5-03
(0064)
PID Output PID Output
All Modes
Displays PID control output.
10 V: 100%
(-10 to +10 V)
0.01%
U5-04
(0065)
PID Setpoint PID Setpoint
All Modes
Displays the PID setpoint.
10 V: 100%
(-10 to +10 V)
0.01%
B.15 U: Monitors
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
525