Yaskawa CIMR-UU4A0216F [262/644] The output opens when the output frequency or motor speed clv clv pm rises above the detection level set in l4 03 plus the detection with set in l4 04 the terminal remains open until the output frequency or motor speed falls below the level set in l4 03 the detection level l4 03 is a signed value detection works in the specified direction only

Yaskawa CIMR-UU4A0014F [262/644] The output opens when the output frequency or motor speed clv clv pm rises above the detection level set in l4 03 plus the detection with set in l4 04 the terminal remains open until the output frequency or motor speed falls below the level set in l4 03 the detection level l4 03 is a signed value detection works in the specified direction only
L4-04
L4-04
Frequency
reference
Speed Agree 2
ON
OFF
Output Frequency
or Motor Speed
Figure 5.72 Speed Agree 2 Time Chart
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 290 for more details.
Setting 14: User-Set Speed Agree 2 (f
ref
/f
set
Agree 2)
The output closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within
the speed agree width (L4-04) of the programmed speed agree level (L4-03).
Status Description
Open Output frequency or motor speed and frequency reference are both outside the range of L4-03 ±L4-04.
Closed Output frequency or motor speed and the frequency reference are both within the range of L4-03 ±L4-04.
Note: The detection level L4-03 is a signed value; detection works in the specified direction only.
Frequency reference + L4-04
Frequency reference – L4-04
L4-03
L4-03 + L4-04
L4-03 – L4-04
Frequency
reference
0 Hz
OFF OFF
ON ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
Figure 5.73 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agree Detection Level and Detection Width (+/-) on page 290 for more details.
Setting 15: Frequency Detection 3
The output opens
when the output frequency or motor speed (CLV, CLV/PM) rises above the detection level set in L4-03 plus
the detection with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set
in L4-03. The detection level L4-03 is a signed value; detection works in the specified direction only.
Status Description
Open Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
5.7 H: Terminal Functions
262
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual