Daikin REYQ14PY1B [104/137] D057885

Daikin REYQ8PY1B [104/137] D057885
3
1
4
VRV Systems • Outdoor Units
103
Outdoor Units • VRV HEAT RECOVERY • REYQ8-48P7Y1B
4 Dimensional drawing & centre of gravity
4 - 1 Dimensional drawing
REMQ14,16P
3D057585A
(Pitch of foundation bolt holes)
(DETAIL FOR FRONT SIDE)
(DETAIL FOR BOTTOM SIDE)
(knock-out hole)
(knock-out hole)
(knock-out hole)
(knock-out hole)
(knock-out hole): pressure equalizer pipe only.
NOTES
1 For piping connection method (front and bottom sides) see
the installation manual.
2 Piping connection diameter for field connection.
3 shows the dimensions after fixing the accesory pipes.
(knock-out hole)
4-15 x 22.5-mm-Oblong holes
(foundation bolt hole)
No. Parts name Remarks
4
Pressure equalizer pipe
connection port.
19.1
Brazing connection.
See note 2
5
Grounding terminal
inside of switch box (M8)
6 Power cord routing hole (side) 62
No. Parts name Remarks
7 Power cord routing hole (front) 45
1
Liquid pipe connection port.
12.7
Brazing connection.
See note 2
8 Power cord routing hole (front) 27
9
Power cord routing hole (bottom)
65.5
2
Suction gas pipe connection port.
28.6 Brazing connection.
See note 2
10 Wire routing hole (front) 27
11 Pipe routing hole (front) See note 1.
3
High and low pressure gas pipe
connection port
22.2
Brazing connection.
See note 3
12 Pipe routing hole (bottom) See note 1.
13
Pipe routing hole (bottom) 50 See note 1.
(Pitch of foundation bolt holes)
3D057885
(Pitch of foundation bolt
holes)
REYQ18,20,22,24P
(Pitch of foundation bolt
holes)
4-15X22,5-mm-Oblong holes
4-15X22,5-mm-Oblong holes
(foundation bolt hole)(foundation bolt hole)
(Pitch of foundation bolt
holes)
Outdoor unit 1 Outdoor unit 2
20 or more
<Front>
<suction side>
10 or more
300 or more
(Front)
500 or more 20 or more
10 or more
Notes:
1 Heights of walls
Front: 1500 mm
suction side: 500 mm
Side: Height unrestricted.
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35°C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35°C.
- Operating over Max. operating load (In case of causing a heavy heating load at indoor unit side).
2 If the above wall heights are exceeded then h1/2 and h2/2 should be added to the front and suction side service spaces respectively as shown in the figureon
the right.
3 When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing
in mind the need to leave enough space for a person to pass between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4 The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
Model name Outdoor unit 1 Outdoor unit 2
REYQ18P REMQ10P REMQ8P
REYQ20P REMQ12P REMQ8P
REYQ22P REMQ12P REMQ10P
REYQ24P REMQ12P REMQ12P