Daikin REYQ14PY1B [134/137] B c d e f g p 90 m increase the pipe size of b c d e f g

Daikin REYQ14PY1B [134/137] B c d e f g p 90 m increase the pipe size of b c d e f g
3
1
8
VRV Systems • Outdoor Units
133
Outdoor Units • VRV HEAT RECOVERY • REYQ8-48P7Y1B
8 Installation
8 - 3 Refrigerant pipe selection
3P201178-3B
φ 9.5 → φ12.7
φ12.7 → φ15.9
φ15.9 → φ19.1
φ19.1 → φ22.2
φ22.2 → φ25.4*
φ28.6 → φ31.8*
φ34.9 → φ
38.1*
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
p
*If available on the site, use this size. Otherwise it can not be increased.
R =
φ
φ
φ
φ
Total length(m)
of liquid piping
size at φ12.7
Total length(m)
of liquid piping
size at φ6.4
REYQ26PY1
~ ~
R =
a : φ
b : φ
c : φ
d : φ
e : φ
f : φ
g : φ
h : φ
i : φ
j : φ
k : φ
l : φ
m : φ
n : φ
o : φ
p :
φ
r : φ
s : φ
t : φ
u :
φ
(Refer to figure 9)
1.Outdoor unit
2.Main pipes
3.Increase only liquid pipe size
4.First refrigerant branch kit
5.
BS unit
6.
Indoor unit
φ→φ
φ→φ
φ→φ
φ→φ
How to calculate the
additional refrigerant
to be charged
Additional refrigerant to
be charged : R(kg)
R should be rounded
off in units of 0.1 kg.
Total length(m)
of liquid piping
size at 22.2
Total length(m)
of liquid piping
size at 15.9
Total length(m)
of liquid piping
size at 9.5
0.37
0.18
0.059
Total length(m)
of liquid piping
size at 19.1
0.26
0.26
0.022
1.02
HEAT RECOVER SYSTEM
MODEL NAME
THE AMOUNT OF REFRIGERANT
REYQ8 ~ 16PY1
REYQ18 ~ 20PY1
REYQ22 ~ 24PY1
REYQ28 ~ 30PY1
REYQ32 ~ 40PY1
REYQ42PY1
REYQ44 ~ 46PY1
REYQ48PY1
3.6kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
3.5kg
4.0kg
4.5kg
REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT
INDOOR
CONNECTION
CAPACITY
MODEL NAME
REYQ8
REYQ34
48PY1
32PY1
MORE THAN 100%
120% OR LESS
MORE THAN 120%
130% OR LESS
0.5kg
0.5kg 1.0kg
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : REYQ34PY1
Total capacity of indoor unit : 116%
19.1 × 30m
19.1 × 20m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 10m
9.5 × 20m
9.5 × 20m
9.5 × 20m
9.5 × 10m
9.5 × 3m
6.4 × 10m
6.4 × 10m
12.7 × 3m
9.5 × 3m
15.9 × 1m
( 50 × 0.26 + 1 × 0.18 + 3 × 0.12 + 156 × 0.059 + 20 × 0.022 )×1.02 + 3.0 + 0.5
a, b u r c~n, s, t o, p
REYQ34PY1 116%
= 27.148 27.1kg
Round off in units of 0.1 kg.
Note 1.
When the equivalent pipe length between outdor and indoor units is 90m or
increased according to the right table.
(Never increase suction gas pipe and HP/LP gas pipe.)
System
Liquid pipe
REYQ8 ~ 10PY1
REYQ12 ~ 16PY1
REYQ18 ~ 24PY1
REYQ26 ~ 48PY1
9.5
12.7
12.7
15.9
15.9
19.1
19.1
22.2
Note 2. Allowable length after the first refrigerant branch kit to indoor units is 40m or less, however it can be extended up to 90m if all the following conditions are satisfied. (In case of “Branch with REFNET joint”)
Required Conditions
Example Drawings
1.
It is necessary to increase the pipe size between the first branch kit
and the final branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must not
be increased.
2.
For calculation of Total extension length, the actual length of
above pipes must be doubled. (except main pipe and the pipes
that are not increased)
3. Indoor unit to the nearest branch kit 40 m
4. The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor unit
to the nearest indoor unit]
40 m
8 b+c+d+e+f+g+p
90 m
increase the pipe size of b, c, d, e, f, g
a+b×2+c×2+d×2+e×2+f×2+g×2
+h+i+j+k+l+m+n+p
1000 m
h, i, j....... p
40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)-(a+h)
40 m
Increase the pipe size as follows
Outdoor unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
H1