Function 109
2.5 Outdoor Unit Fan Control in Cooling Operation
While in cooling operation, if the outdoor temperature is low, this mode provides high-pressure
control using the outdoor unit fan to retain appropriate liquid pressure, thus ensuring refrigerant
circulation rate to be supplied to indoor units.
Hold the current
step on outdoor
unit fan
-1 step on
outdoor unit fan
+1 step on
outdoor unit fan
PI control
PI control
Lapse of 20 sec.
Lapse of 20 sec.
Fan step 7
Pc>3.08MPa
Pc>3.18MPa
Fan step 8
Pc>3.28MPa
Fan step 9
PI control
PI control
PI control