Daikin REYQ34PY1 [121/438] Heat exchanger control

Daikin REYQ18PY1 [121/438] Heat exchanger control
Basic Control Si37-701
110 Function
2.6 Heat Exchanger Control
While in heating or cool/heat simultaneous operation, ensure target condensing and
evaporating temperature by changing over the air heat exchange of outdoor unit to the
evaporator or the condenser in response to loads.
Note: The mode for an single type and a multi type with two units connected is Unit 1 Mode and Unit 2
Mode. Unit 1 Mode, Unit 2 Mode and Unit 3 Mode are available only for three unit connected
multi type.
[Independent system]
[Multi outdoor unit system]
Mode Unit 1 Unit 2 Unit 3
*
“GR” is a numeric value representing the current balance state
that is calculated from the target condensing temperature,
target evaporating temperature, current condensing
temperature, and current evaporating temperature.
A1 Condenser Condenser Condenser
A2 Condenser Condenser Evaporator
A3 Condenser Evaporator Not in use
A4 Condenser Evaporator Evaporator
B1 Not in use Evaporator Not in use
B2 Evaporator Evaporator Not in use
B3 Evaporator Evaporator Evaporator
Note 1. "GR" is a numeric value
representing the current
balanced condition and
calculated from target
condensing temperature,
target evaporating
temperature, current
condensing temperature,
and current evaporating
temperature.
Outdoor unit
Left side
Condenser
Right side
Condenser
Outdoor unit
Left side
Evaporator
Right side
Outdoor unit
Left side
Evaporator
Right side
Evaporator
Outdoor unit
Left side
Evaporator
Right side
Condenser
GR > 25 GR < -20
GR > 25
GR < -20
GR > 15 GR < -10
GR > 15 GR < -10
A1
A2
Outdoor unit
Note 1. "GR" is a numeric value representing the current balanced
condition and calculated from target condensing temperature,
target evaporating temperature, current condensing
temperature, and current evaporating temperature.
Note 2. On the system with two outdoor units, if there is no step for the
destination of transition, that step will be skipped.
1
Condenser
2
Condenser
3
Condenser
B1
Outdoor unit
1
2
Evaporator
3
Outdoor unit
1
Condenser
2
Condenser
3
Condenser
Outdoor unit
1
Condenser
2
Condenser
3
Outdoor unit
1
Condenser
2
Evaporator
3
Evaporator
GR > 25 GR < -20
GR > 25
GR < -20
GR > 25
A3
GR > 15 GR < -10
B2
Outdoor unit
1
Evaporator
2
Evaporator
3
Outdoor unit
1
Evaporator
2
Evaporator
3
Evaporator
GR > 15 GR < -10
B3
A4
GR > 15 GR < -10