Daikin REYQ34PY1 [283/438] J6 outdoor unit malfunction of thermistor r4t or r12t for outdoor unit heat exchanger

Daikin REYQ34PY1 [283/438] J6 outdoor unit malfunction of thermistor r4t or r12t for outdoor unit heat exchanger
Troubleshooting by Indication on the Remote Controller Si37-701
272 Troubleshooting
3.29
J6
Outdoor Unit: Malfunction of Thermistor (R4T or
R12T) for Outdoor Unit Heat Exchanger
Remote
Controller
Display
J6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Defect of thermistor (R4T or R12T) for outdoor unit coil
Defect of outdoor unit PC board (A1P)
Defect of thermistor connection
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P405.
(V3074)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
R4T or R12T from the
indoor unit PC
board. (1.8k
to 800k)
Replace outdoor unit PC board
(A1P).
Connect the connector and turn on
again.
NO
NO
Replace the thermistor R4T or
R12T.
YES
YES
Connector
is connected to X30A
of outdoor unit PC
board (A1P).
Confirm which thermistor is
abnormal using outdoor unit
"monitor mode".
(Refer to P226~227)