Daikin REYQ34PY1 [294/438] L5 outdoor unit momentary overcurrent of inverter compressor

Daikin REYQ34PY1 [294/438] L5 outdoor unit momentary overcurrent of inverter compressor
Si37-701 Troubleshooting by Indication on the Remote Controller
Troubleshooting 283
3.37
L5
Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
Remote
Controller
Display
L5
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction
Decision
Conditions
When an excessive current flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PC board