Si37-701 Protection Control
Function 125
[Heating Operation and Simultaneous Cooling / Heating Operation]
The following control is performed in the entire system.
Pc_max indicates the maximum value within the system.
Pc_max<2.94MPa
Pc_max
>3.42MPa
Pc_max>3.31MPa
Pc_max>3.31MPa
&
Pc_max>3.64MPa
When occurring 3 times within
30 min., HPS is activated without high
pressure standby, thus outputting the
malfunction code “E3.
Normal Operation
After 10 sec.
High pressure
standby
Compressor step:
7 STEP down
Set the compressor
step to STEP 1
When high
pressure is limited