Daikin REYQ34PY1 [335/438] Uh malfunction of system refrigerant system address undefined

Daikin REYQ34PY1 [335/438] Uh malfunction of system refrigerant system address undefined
Troubleshooting by Indication on the Remote Controller Si37-701
324 Troubleshooting
3.57
UH
Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
All models of indoor units
REYQ8P~48P
Method of
Malfunction
Detection
Detect an indoor unit with no address setting.
Malfunction
Decision
Conditions
The malfunction decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Improper connection of transmission wiring between indoor-outdoor units and outdoor-
outdoor units
Defect of indoor unit PC board
Defect of outdoor unit main PC board (A1P or A3P)