Daikin REYQ34PY1 [271/438] F3 outdoor unit abnormal discharge pipe temperature

Daikin REYQ8PY1 [271/438] F3 outdoor unit abnormal discharge pipe temperature
Troubleshooting by Indication on the Remote Controller Si37-701
260 Troubleshooting
3.20
F3
Outdoor Unit: Abnormal Discharge Pipe
Temperature
Remote
Controller
Display
F3
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level (135 °C and above)
When the discharge pipe temperature rises suddenly (120 °C and above for10 successive
minutes)
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PC board