Daikin UATYA180BFC2Y1 [14/534] Zoning dampers installed in rooms considered to determine the minimum room area must be electrically powered at all times after installation other than when servicing to be effective for safety

Daikin UATYA40BBAY1 [14/534] Zoning dampers installed in rooms considered to determine the minimum room area must be electrically powered at all times after installation other than when servicing to be effective for safety
Translation from original instructions
Packaged Rooftop
14
We reserve the right to make changes without any prior notice.
UATYA
4P645202-1
The unit is equipped with a refrigerant detection system that complies with Annex LL of the IEC 60335-2-40:2018,
which position has been checked according to test reported in Annex MM of IEC 60335-2-40:2018.
When the refrigerant detection system detects a leak, the following will be initiated by the unit:
disable the compressor operation unless the compressors;
Supply and return (if present) fan control will be set to to constant airow logic with a x airow value. The fans
will operate continuously even if time tables are set. This in order to not let the airow to go below "Q
min
" (see
below);
Energize a dedicated relay in the electrical cabinet in order to fully open any external zoning dampers;
Set the dampers (if installed on the appliance) in order to have a full intake of fresh air and a full expulsion of the
return air.
External zoning dampers, if present, must be connected to this relay in order to be open when a leak
is detected
Zoning dampers installed in rooms considered to determine the minimum room area must be
electrically powered at all times after installation, other than when servicing, to be e󰀨ective for safety.
The refrigerant detection system and controls will maintain the above action until at least 5 min after the refrigerant
detection system has reset. Building re and smoke systems may override this function.
If the leak detector detects a leak, the above operations will be initiated even if the unit is turned OFF
by button, by BMS or by digital input.
In addition to what above another dedicated relay is present in the unit electrical cabinet and
connected directly to the leak detector alarm. This relay can be used to monitor the leak detector
alarm even in case of a unit control board fault.
The minimum circulation airow (Q
min
) circulated to the total conditioned space, expressed in m
3
⁄h, must be in
accordance with the following table:
Unit
For units without hot gas post heating coil For units with hot gas post heating coil
m
c
Q
min
m
c
Q
min
[kg] m
3
/h [kg] m
3
/h
UATYA25 7 - 1368 8,3 - 1613
UATYA30 10 - 1954 11,3 - 2208
UATYA40 12 - 2345 13,7 - 2680
UATYA50 15 - 2932 17 - 3326
UATYA60 18 - 3518 21 - 4095
UATYA70 18 - 3518 21 - 4095
UATYA80 23 - 4495 26,9 - 5255
UATYA90 24 - 4691 28 - 5479
UATYA100 28 - 5472 32,3 - 6315
UATYA110 30 - 5863 34,7 - 6783
UATYA120 36 - 7036 41,2 - 8059
UATYA140 19 19 3713 23,1 23,1 4515
UATYA150 19 19 3713 23,1 23,1 4515
UATYA160 23 23 4495 27,9 27,9 5453
UATYA180 25 25 4886 25 25 4886
UATYA190 25 25 4886 25 25 4886
Whenever the ow, measured by the di󰀨erantial air presssure tranducer, falls below the values
reported in the table above, the airow alarm from di󰀨erential pressure transducer will be displayed on
the unit control and the unit will be stopped.
The supply and return air shall be directly ducted to the conditioned space. Open areas such as false ceilings shall
not be used as a return air duct.