Chapter 6 Parameter Description 111
maximum step length of adjustment is 1.00Hz.
1: Without integral function. When the operation panel / adjustment is used to set the frequency, the
step length of the adjustment is fixed to 0.1Hz.
Note: When operating under process closed loop PID, the closed loop reference also can be adjusted
with operational panel /. Then adjustment volume of / is regarded as analog superimposed upon
closed loop reference. The minimum step size is 1mV.
Display of operational panel
Unit place
Action when power failure
0: Mains loss save;
1: Zero clearing upon mains loss
Tens place
Action when shutdown
0: Maintained when shutdown;
1: Reset when deceleration shutdown;
2: Reset when standby
Hundreds
place
Terminal UP/DN regulation setting
0: Only valid when main reference is P0.05
open loop digital frequency setting;
1: Valid during adjustment;
2: Invalid during adjustment
Thousands
place
0: With integral function;
1: Without integral function
Pb.10 and Pb.11 are the same as the usage of operational panel /. For functions of terminal UP/DN,
refer to instructions of P5.00~P5.06.
0: No action after power resumes normal.
1: Action after power resumes normal.
The function supports automatic operation of the inverter upon power resume normal after power failure.
Be careful in using this function.
When restart after power failure is selected, the inverter will operate automatically after power on under
any operating command reference mode, such as operation panel operating command reference,
terminal operating command reference or host computer operating command reference.
When restart after power failure is selected, if P0.06=1 and the running terninal is enable when power on,
the inverter will be run after power resumes normal.
Note: To ensure this function is valid under terminal operating command reference mode, please do not
change the status of operating command terminal during shutdown.
Pb.10
Terminal UP/DN digital regulating frequency control
0~0221(0001)
Pb.11
Terminal UP/DN integral rate
0.1~50.0 s(2.0s)
Pb.15
Restart automatically after power resumes normal
0~1(0)
Pb.16
Waiting time for restart
0.0~20.0 s (05.s)
Pb.17 Pre-set frequency
0.00~300.00 Hz (0.00Hz)
Pb.18 Pre-set frequency operating time 0.0~3600.0 s(0.0s)