Tecorp HC2V9G4075 [24/182] Product series

Tecorp HC2V9G21P5 [24/182] Product series
High Performance Vector Control Inverter/Torque Control User Manual
2 Chapter 1 Introduction toV8/V9 Series Inverter
1.3 Product Series
G-4□□□ Three-phase 400V Constant torque/heavy-duty application
Power (kW) 40P7
41P5
42P2
43P7
45P5
47P5
4011
4015
4018
4022
4030
4037
4045
4055
4075
Motor
power (kW)
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
Voltage (V) Three-phase 0 to rated input voltage
Rated current (A)
2.5
3.8
5.5
9
13
17
24
30
39
45
60
75
91
112
150
Output
Overload
capacity
150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes
(inverse time lag feature)
Rated
voltage/frequency
Three-phase 380V/480V; 50Hz/60Hz
Allowable voltage
range
323V ~ 528V; Voltage unbalancedness 3%; allowable frequency fluctuation: ±5%
Input
Rated current (A)
3.5
6.2
9.2
14.9
21.5
27.9
39
50.3
60
69.3
86
104
124
150
201
Braking unit Built-in as standard Built-in as option
Protection class IP20
Cooling mode Self-cooling
Forced air convection cooling
Power (kW) 90 110
132
160
200
220
280
315
355
400
Motor
power (kW)
90 110
132
160
200
220
280
315
355
400
Voltage (V) Three-phase 0 to rated input voltage
Rated current (A)
176
210
253
304
380
426
520
585
650
730
Output
Overload
capacity
150% 1 minute, 180% 10 seconds, 200% 0.5 second, interval: 10 minutes
(inverse time lag feature)
Rated
voltage/frequency
Three-phase 380V/480V; 50Hz/60Hz
Allowable voltage
range
323V ~ 528V; Voltage unbalancedness 3%; allowable frequency fluctuation: ±5%
Input
Rated current (A)
160*
196*
232*
282*
352*
385*
491*
552*
624*
704*
Braking unit External braking unit needed
Protection class IP20
Cooling mode Forced air convection cooling
* V9-G/P4090 and above products are equipped with external DC reactor as standard.