High Performance Vector Control/Torque Control Inverter User Manual
Appendix C FAQ 149
Appendix C FAQ
I. In the case of vector control 2 with encoder speed feedback or torque control, why did the inverter
have too large running current or report E.oL1 error?
A: Check the software setup:
A: (1) Check if the motor parameters are properly set;
A; (2) Check if the number of pulses per turn of the encoder Pd.21 is properly set;
A: (3) Check if the deceleration ratio between motor and encoder Pd.24 is properly set;
A: (4) If the above three parameters are properly set, change the value of Pd.22. If it is 0, change it to 1;
while if it is 1, change it to 0.
Check the hardware connection:
A: (1) Check if the PG card matches the encoder;
A: (2) Check if the PG card and the encoder are properly connected, check if there is any loose connection
or broken wire;
A: (3) Check if the connectors of the PG card and inverter control board are loose or dislocated;
A: (4) Check if the control lines for the V9-G-4018/P-4022 and current sensor of above power class are
loose or dislocated.
II. Why did the inverter have abnormal operation upon vector control 2 without encoder speed
feedback?
A: (1) Check if there exists large difference between the power class of the motor and that of the inverter;
A: (2) Check if parameter auto-tuning has been performed under vector control 2. For details, refer to the
setting process for parameter auto-tuning in Appendix B.
A: (3) Check if the control lines for the V9-G-4018/P-4022 or current sensor of above power class are loose
or dislocated.
III. Why did the inverter have abnormal operation upon vector control 2 without encoder speed
feedback or vector control 2 with encoder speed feedback?
A: (1) Check if there exists large difference between the power class of the motor and the inverter;
A: (2) Check if parameter auto-tuning has been performed under vector control 2. For details, refer to the
setting process for parameter auto-tuning in Appendix B.
A: (3) Check if the torque reference channel and speed limiting channel are properly set. For details, refer to
setting process for torque control in Appendix B.
A: (4) Check if the control lines for the V9-G-4018/P-4022 or current sensor of above power class are loose
or dislocated.
IV. Why did the inverter have abnormal operation upon vector control 1?
A: (1) Check if parameter auto-tuning has been performed under vector control 1. For details, refer to the
setting process for parameter auto-tuning in Appendix B.