Tecorp HC2V9G4075 [76/182] Group pb enhanced function parameter

Tecorp HC2V9P47P5 [76/182] Group pb enhanced function parameter
High Performance Vector Control/Torque Control Inverter User Manual
54 Chapter 5 List of Parameters
PA.18
Fault shield and alarm
attribute setting 3
2000
0000 ~ 2222
/ ×
LED ones place: +10V output error
LED tens place: Analog input error
LED hundreds place: Motor over
temperature (PTC)
LED thousands place:
Communication failure 1(operation
panel 485)
0: Fault is not shileded, stopped
upon fault;
1: Fault is not shielded, non-stop
upon fault;
2: Fault is shielded, no alarm and
no
stop
PA.19
Fault shield and alarm
attribute setting 4
0002
0000 ~ 2222
/ ×
LED ones place: Communication
failure 2(terminal 485)
LED tens place: Version
incompatible
LED hundreds place: Reserve;
LED thousands place: Reserve;
0: Fault is not shileded, stopped
upon fault;
1: Fault is not shielded, non-stop
upon fault;
2: Fault is shielded
, no alarm and no
stop
PA.20
Fault locking function
selection
0 0 ~ 1 / ×
0: Fault is not locked;
1: Fault is locked
PA.21 Automatic reset times 0 0 ~ 20 / × 0 ~ 20
PA.22 Automatic reset interval 2.0
2.0 ~20.0 s × 2.0 ~ 20.0s
Group Pb Enhanced Function Parameter
Pb.00
Hopping frequency 1 lower
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower frequency limit (P0.13
~ P0.14)
Pb.01
Hopping frequency 1 upper
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower frequency limit (P0.13
~ P0.14)
Pb.02
Hopping frequency 2 lower
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower frequency limit (P0.13
~ P0.14)
Pb.03
Hopping frequency 2 upper
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower frequency limit (P0.13
~ P0.14)
Pb.04
Hopping frequency 3 lower
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower freq
~ P0.14)
Pb.05
Hopping frequency 3 upper
limit
0.00
0.00 ~ 300.00
Hz ×
Upper / lower frequency limit (P0.13
~ P0.14)
Pb.06
Single step under without
integral function
0.1
0.0 ~ 10.00
Hz 0.0 ~ 10.00Hz
Pb.07 Magnification selection 00
00 ~ 11 / ×
Ones place: Acceleration /
deceleration time
0: X1; 1: X10
Tens place: Reserved
Pb.08
Operation panel / digital
regulating f
requency control
0001
0000 ~ 0221
/
Ones place: Action upon power off
0: Save upon power off;
1: Clear upon power off
Tens place: Action upon stopping
0: Hold upon stopping;
1: Clear upon stop;
2: Clear upon standby
Hundreds place: / setting via
operation panel
0: Only enabled when main input is
P0.05 open loop digital frequency
input;
1: Adjustment is valid;

Содержание