Tecorp HC2V9G4075 [46/182] Functions of control circuit terminals

Tecorp HC2V8P4110 [46/182] Functions of control circuit terminals
High Performance Vector Control/TorqueControl Inverter User Manual
24 Chapter 3 Wiring of Incerter
3.8 Functions of Control Circuit Terminals
Type
Terminal
symbol
Terminal function
description
Technical specification
485+
Positive end of 485
differential signal
485−
Negative end of 485
differential signal
Rate: 4800/9600/19200/38400/57600bps
Up to 32 sets of equipment can be paralleled. Relay
shall be used if the number exceeds 32.
Maximum distance: 500m (adopt standard twisted
shielding cable)
Terminal 485
GND
Shielding grounding of 485
communication
Internal isolated with COM
When used for communication connection with host
computer, it is the same as termin
al 485.
Operation
panel 485
CN7 485 port of operation panel
The maximum distance is 15m for the communication
connection of operation panel
(adopt standard twisted non-shielding network cable)
+24V +24V
24V±10%, internal isolated with GND,
Maximum load: 200mA, with overload and short circuit
protection
PLC
Common end of
multi-
functional input terminal
Short circuited with +24V upon delivery
X1~X6
Multi-functional input
terminals 1 ~ 6
Input specification: 24VDC,5mA
Frequency range: 0~200Hz
Voltage range: 24V±20%
X7/DI
Multi-functional input or pulse
input
Multi-functional input: same as X1~X6
Pulse input: 0.1Hz~50kHz; voltage range: 24V±20%
Digital input
COM +24V grounding
Internal isolated with GND
Y1 Open collector output
Voltage range: 24V±20%, maximum input current: 50mA
Y2/DO
Open collector: Same as Y1
Pulse output: 0~50kHz; voltage range: 24V±20%
Digital output
COM
Open collector output
common end
Internal isolated with GND
+10V
Analog input reference
voltage
10V ±3%, internal isolated with COM,
Maximum output current: 10mA, with short circuit and
overload protection
AI1 Analog input channel 1
0~20mA: Input impedance 500Ω, maximum input
current: 30mA
0~10V: Input impedance 20kΩ, maximum input
voltage : 15V
Resolution: 12 bits (0.025%)
0~20mA or 0~10V analog input can be selected
through jumper.
AI2 Analog input channel 2
Same as AI1
AI3 Analog input channel 3
-10V~10V: Input impedance 20kΩ
Resolution: 12 bits (0.025%)
Maximum input voltage: ±15V
Analog input
GND Analog grounding
Internal isolated with COM
AO1 Analog output 1
0~20mA: allowable output impedance 200~500Ω
0~10V: allowable output impedance ≥10kΩ
Output precision: 2%, resolution: 10 bits (0.1%)
with short circuit protection function,
0~20mA or 0~10V analog output can be selected
through jumper.
AO2 Analog output 2
Same as AO1
Analog
output
GND Analog grounding
Internal isolated with COM

Содержание

Скачать