Daikin EWAP460MBYN [211/452] Thermostat control

Daikin EWAP200MBYN [211/452] Thermostat control
ESIE05-07 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–15
3
2
4
5
1
2.4 Thermostat Control
Introduction The thermostat control is used to generate a load -up or load-down according to the active thermostat,
if the load-up respectively load-down timer is finished (this means gone to "0").
The thermostat can be set to regulate on different signals:
P Signal from the water sensor at the inlet of the evaporator.
P Signal from the water sensor at the outlet of the evaporator.
P Signal from the water sensor at the inlet of the condenser.
There are several possible functions for the thermostat control:
P Cooling: inlet evaporator control.
P Cooling: outlet evaporator control.
P Heating: inlet condenser control.
P Double thermostat: inlet condenser and inlet evaporator control.
P External analog signal. ( 0 - 1V, 0 - 10V, 4 -20 mA ,0 - 20 mA ).
P Floated setpoint.
P Thermostat: This function is only available on ER units by use of air sensor
(No exterminal capacity control possible).
Overview of the
possibilities
Air-cooled
cooling only
Evaporator-less Water-cooled Condenser-less
EWAP EWTP ERAP EWWD EWLD
CO HR CA HP RC
Cooling mode Inlet water step X X X X
Outlet water step X X X X
Floated Setpoint X X X
Thermostat X
External analog
signal
XX X X
Heating mode Inlet water step X X
External analog
signal
XX
Double thermo-
stat mode
Inlet water step X
External analog
signal
XX
Manual control X X X X X
ESIE05-07.book Page 15 Wednesday, October 11, 2006 10:42 AM