Daikin EWAP460MBYN [301/452] Changeable analogue input

Daikin ERAP150MBYNN [301/452] Changeable analogue input
ESIE05-07 The Functional Controller for DICN
Part 2 – Functional Description 2–105
3
2
4
5
1
3.21 Changeable Analogue Input
MSOption = yes
(network units)
MSOption = no
(standalone units)
1. Master slave mixed
outlet water temperature
sensor
Only for AI1 of the master unit of
a DICN setup
Only for AI1 of the master unit of
a DICN setup
2. Setpoint signal AI1 of Slave1! (0-1V) AI1 of unit (0-1V)
(not possible on master unit or
slave 2/3)
3. HR selection based
on the condenser inlet
water
If master unit is a heat recovery
unit AND
DICN is working on
outlet water control then:
P AI3 needs to be programmed
as MS outlet water E
P HR selection has to be used
with external thermostat
(changeable Input)
AI1 can be programmed as HR
inlet water C
ESIE05-07.book Page 105 Wednesday, October 11, 2006 10:42 AM