2.26 BMS Function
Introduction BMS stands for Building Management Systems. These systems were developed for centralized
overview and control of technical installation for complete sites.
The Daikin BMS option makes it possible to connect the Daikin chillers to a larger control system. The
necessary tools for this communication are the Gateway and the address card.
In this chapter we will give a short overview of the possibilities and settings for the BMS function.
For more detailed information we refer to the service manual "BMS option for Daikin water chillers"
Function
description
In the service menu it is possible to set the parameter "BMS control allowed". If this parameter is "YES"
then the supervisor can read and write parameters from and to the unit. If however the parameter is
set to "NO" then the supervisor can only read parameters from the unit.
For communication both the address card and the Gateway create a database with the variables.
P From address card to Gateway
P From Gateway to supervisory BMS
The BACnet and Modbus-Jbus protocols do not distinguish integer from analogue variables. Therefore
the integer and analogue variables from the address card will be put together in the analogue variables
in the Gateway database.
Variable type Maximum number
Digital 200
Analogue 128
Integer 128
Variable type Maximum number Corresponding BACnet object
Digital 200 Binary value
Analogue 256 Analogue value
ESIE05-07.book Page 71 Wednesday, October 11, 2006 10:42 AM