Daikin EWAP460MBYN [377/452] Copy from pco to the software key

Daikin EWAP400MBYN [377/452] Copy from pco to the software key
ESIE05-07 Procedure for software upload/download
Part 3 – Troubleshooting 3–21
33
4
5
1
4.3 Copy from pCO² to the Software Key
P Switch off the pCO
2
and remove the "expansion memory" cover with a screwdriver (see Fig. 1)
P Set the key selector on
P Insert the key in the corresponding pin connector as shown. (see Fig. 2)
P Press simultaneously the buttons UP an DOWN then supply the pCO
2
P Check the LED on the key is on (green color )
P Wait until the request of copying appears on the LCD display, then release the buttons and confirm
by pressing ENTER.
P If the application includes a password to protect the software, use the UP and DOWN buttons on
the terminal to enter the correct password. Then press enter.
P The data transfer operation takes about 50s using the 1MB key and 100s using the 2MB one.the
display will show a progressive series of numbers.
P Once copied the application program starts, then switch off the pCO
2
, remove the key, put the
cover in its place and switch on the pCO
2
again,
P Now the key has the program transferred by the pCO
2
.
Fig. 1 Fig. 2