Daikin EWAP460MBYN [39/452] Esie 05 07 general outline

Daikin EWWD180MBYNN [39/452] Esie 05 07 general outline
ESIE 05-07 General Outline
Part 1 – System Outline 1–27
3
1
4
5
Notes 1. Nominal cooling capacity at Eurovent conditions: Evaporator = 12°C/7°C; ambient = 35°C.
2. Nominal cooling power input at Eurovent conditions: Evaporator = 12°C/7°C; ambient = 35°C.
3. Min. required water volume for standard thermostat settings and at nominal conditions.
4. Nominal cooling capacity and heat recovery capacity during heat recovery mode according to
EN14511.
5. Dimension values between brackets include installation space of delivered filter.
Liquid line
solenoid valves
2 x (16.1 VA -70 mA) inrush current = 130 mA 2 x (3 x (16.1 VA -70 mA))
inrush current = 130 mA
Capacity sole-
noid valves
1 x (16.1 VA -70 mA) inrush current = 130 mA 2 x (16.1 VA -70 mA) inrush current =
130 mA
Evaporator heater tape
Supply Voltage
230V+/-10% V
Recommended
fuses
2x2A 2x4A
Condenser heater tape
Supply Voltage
230V+/-10% V
Recommended
fuses
2x2A 2x4A
Model
EWTP
110MBYNN
EWTP
140MBYNN
EWTP
160MBYNN
EWTP
200MBYNN
EWTP
280MBYNN
EWTP
340MBYNN
EWTP
400MBYNN
EWTP
460MBYNN
EWTP
540MBYNN
ESIE05-07.book Page 27 Wednesday, October 11, 2006 10:42 AM