Daikin EWAP460MBYN [242/452] Capacity limitation

Daikin EWWD440MBYNN [242/452] Capacity limitation
Functional Control for a Standalone Unit ESIE05-07
2–46 Part 2 – Functional Description
3
1
2
4
5
2.11 Capacity Limitation
Introduction This function allows you to limit the capacity of the chiller. Depending on the adjusted mode, it is
possible to control the capacity limitation via remote digital input, programmable schedule timer. From
software version V3.0M6 onwards it is also possible to activate and deactivate the limitations manually
or through BMS.
The limitation settings can be set in the user settings menu. In manual mode this function is not active.
If the limitation of that circuit is activated then:
P It is not possible to go to a higher capacity than the limitation. The compressor will stop uploading
when compressor capacity > (limit x - 5 seconds download).
P If the present capacity is higher then the limitation than the compressor will download till:
compressor capacity < (limit x - 5 seconds download).
Remote digital
input mode
There are four different possible limitation settings which can be set in the user settings menu (L1CIR1
CIR2, L2 CIR1 CIR2, L3 CIR1 CIR2 and L4 CIR1 CIR2).
To activate the remote digital input mode just set one of the digital inputs to the desired setting in the
service menu (DI1, DI2, DI3 and DI4) (possible settings: CAP. LIMIT 1, 2, 3 or 4) and connect the
limitation switch to the right remote digital input terminals.
Schedule timer
mode
The schedule timer screen of the user settings menu allows the user to define the capacity limitation
setting according to a programmed time.
P MON, TUE, WED, THU, FRI, SAT and SUN: are used to define to which group each day of the
week belongs (-/G1/G2/G3/G4).
P For each of the four groups up to nine actions can be set, each with their respective timing.
P Beside these four groups there is also a holiday period group which is set the same way as the
other groups. Up to 12 holiday periods can be entered in the HD PERIOD screen. During these
periods the schedule timer will follow the settings of the holiday period group.
Unit Limitation
LIM 1
This unit Limitation “ LIM1” allows the user to use the limitation setting 1 (L1, CIR1, CIR2) without the
need of a digital input, or schedule timer. To activate this unit Limitation just set “ Mode LIM1” and
change the capacity of L1, CIR1 and CIR2 to the desired value.
Remark: Only the first limitation setting (L1) can be used in “LIM1” mode.