Daikin EWAP460MBYN [376/452] Copy from the software key to pco

Daikin EWWD180MBYN [376/452] Copy from the software key to pco
Procedure for software upload/download ESIE05-07
3–20 Part 3 – Troubleshooting
3
1
3
4
5
4.2 Copy from the Software Key to pCO²
P Switch off the pCO
2
and remove the "expansion memory" cover with a screwdriver (see "Copy from
pCO² to the Software Key" on page 3–21/Fig. 1)
P Set the key selector on
P Insert the key in the corresponding pin connector as shown. (see "Copy from pCO² to the Software
Key" on page 3–21/Fig. 2)
P Press simultaneously the buttons UP an DOWN then supply power to the pCO
2
P Check the LED on the key is on (red color )
P Wait until the request of copying appears on the LCD display, then release the buttons and confirm
by pressing ENTER.
P The data transfer operation takes about 50s using the 1MB key and 100s using the 2MB one.the
display will show a progressive series of numbers.
P Once copied the application program starts, then switch off the pCO
2
, remove the key, put the
cover in its place and switch on the pCO
2
again,
P Now the pCO
2
works with the program transferred by the key.