Part 2 – Functional Description 2–145
3
2
4
5
1
4.11 History Menu
Introduction The history menu contains all the information concerning the latest shutdowns. The structure of those
menus is identical to the structure of the safety menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safety menu is copied into the history menu. The last
20 errors or warnings are recorded and can be read out.
Additionally the number of safeties that already occurred on each circuit can be consulted on the first
line of the history screens.
Screen 1
When in this main history screen it is possible to go to sub screens for more detailed information. To
access these sub screen press the
q key as many times as needed to reach the desired sub screen.
Remark: The sub-screens automatically disappear after 5 seconds.
Line n° Display Description
1 UNIT HISTORY:XXX
CIRC 1 HISTORY:XXX
CIRC 2 HISTORY:XXX
NET HISTORY:XXX
U WARN HISTORY:XXX
C1WARN HISTORY:XXX
C2WARN HISTORY:XXX
Indicates the safety.
XXX is the number of the alarm.
2 XXX:XXXXXXXXXXXX Indicates the safety code and its description.
3 XXhXX – XX/XX/XX Indicates time and date of safety.
4 INLSETP1 E: XXX°C or
INLSETP2 E: XXX°C or
OUTSETP1 E: XXX°C or
OUTSETP2 E: XXX°C or
INLSETP1 C: XXX°C or
INLSETP2 C: XXX°C or
SP1E: C: or
SP2E: C: or
THERMOSTAT
MANUAL MODE
HR INL C SENCOR
Indicates the control mode and setpoint at
the moment of shutdown.
ESIE05-07.book Page 145 Wednesday, October 11, 2006 10:42 AM